Número de pieza PVI3000
Descripción Residential/Commercial Grid-Tied Photovoltaic Inverter INSTALLATION AND OPERATION MANUAL
Fabricantes Solectria 
Logotipo Solectria Logotipo



Hay una vista previa y un enlace de descarga de PVI3000 (archivo pdf) en la parte inferior de esta página.


Total 30 Páginas

No Preview Available ! PVI3000 Hoja de datos, Descripción, Manual

http://www.wholesalesolar.com/inverters.html
PVI 3000/PVI 4000
PVI 5000/PVI 5300
INSTALLATION AND OPERATION MANUAL
Residential/Commercial
Grid-Tied Photovoltaic Inverter
© 2008, Solectria Renewables
Subject to Change REV 1.2.3
http://www.wholesalesolar.com/inverters.html

1 page




PVI3000 pdf
PVI 3000/4000/5000/5300
http://www.wholesalesolar.com/inverters.html
Installation and Operation Manual
1 Introduction
The PVI 3000, PVI 4000, PVI 5000 and PVI 5300 are residential/commercial single phase, grid-tied PV
inverters designed to be inter-connected to the electric utility grid. With this manual the PVI 3000 - PVI
5300 can be installed and operated safely. This installation guide is used as reference for commissioning
and as a guideline on how to use the inverter most effectively.
Feeding power into the grid involves conversion of the DC-voltage from the PV-array to grid compatible
AC-voltage by “inverting” DC to AC. This unit feeds power into a standard 240 VAC split phase
electrical system or two legs (phase to phase) of a 208 VAC, 3-phase commercial, industrial or
institutional facility’s electrical system that is connected to the electric utility grid.
If the PV system and inverter are providing the same amount of electrical power that the facility is using
then no power is taken from or fed into the utility grid. If the facility is using more power than the PV
system is providing, then the utility grid provides the balance of power. If the facility is using less power
than the PV system is generating, then the excess is fed into the utility grid.
Be sure to look into local regulations regarding net metering/inter-connection in your local area. Note
that some utilities need to change their revenue kWh meter for proper net metering measurement or
incentives/billing.
Photovoltaic
Array
PVI 3000-5300
Inverter
Electric Utility
Grid
Fig. 1.1 Grid tied inverter application
The string PV concept
The use of string PV concept significantly reduces the cabling costs on a photovoltaic system. The use of strings of several PV
modules in series and one, two, three (or in some cases four) parallel strings of PV modules has proven advantageous by
delivering a high operating voltage to the solar inverter. This advantage is primarily reflected in a higher efficiency of the
inverter. Careful optimization of the overall inverter system’s cost and efficiency lead to the choice of a 600V DC maximum
system voltage for the power levels of the PVI 3000, 4000, 5000 and 5300 for use with 1kW to 7kW PV arrays per inverter.
5
http://www.wholesalesolar.com/inverters.html

5 Page





PVI3000 arduino
PVI 3000/4000/5000/5300
http://www.wholesalesolar.com/inverters.html
Installation and Operation Manual
20” 20”
7.5”
7.5”
WA RNI NG
RISK OF EL ECTRICAL SHOCK
Normall y Gr ounded Condu ctor s Ma y Be
Ung roun de d an d Energize d When a
Ground- Fault is Ind ic at ed."
DO NOT RE MO VE COVER . NO USER
SERVICEABLE PART SINSIDE. REFER
SER VICING TO QU AL IFIE D SERVICE
PERSO NNEL.
BOT H AC A ND DC VO LTAGE SOURCES ARE
TER MINATED INSIDE THI S EQUIPMENT.
EAC H CIRC UIT MU ST BE INDIVIDUALLY
DIS CONNECTE D BEFORE SERVICING.
WHE N THE PH OT OVOLTA IC ARRAY IS
EXP OS ED TO LIGHT, IT SUPPLIESA DC
VOL TA GE TO THIS EQUIP MENT.
DO NOT RE MO VE COVER UNTIL 5 MINUTES
AFT ER DIS CO NN ECTING ALL S OURCESOF
S UP PLY .
VOL TA GE AND FREQUEN CY LIMITS ARE
SET TO TH E CURR EN T UL17 41 STANDARD
AT THE TIME O F SHIP ME NT. RE FER TO
MAN UA L FOR VOLTAGE AND FREQUENCY
SET TING F OR THI S MODE L CHANGE STO
THE SE SETTINGS CA N BE MADEONLY BY
AN AUTHORIZ ED INS TALLER.
36” min
wall
GFDI Fuse
For c on tinued p ro te ctio n ag ainst risk of fire,
rep la ce only with s ame ty pe and ratings of fuse.
39” 39”
Fig2.1.1
Mounting details
Clearances recommended for PVI 3000/4000/5000/5300 inverter installation
The steps listed below describe how to mount the inverter on the wall:
- After taking the inverter out of the cardboard box, you will find the bracket in the bag behind the heatsink. First, the
bracket needs to be removed from the inverter as shown in the figure 2.2.1 below.
11
http://www.wholesalesolar.com/inverters.html

11 Page







PáginasTotal 30 Páginas
PDF Descargar[ Datasheet PVI3000.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
PVI3000Residential/Commercial Grid-Tied Photovoltaic Inverter INSTALLATION AND OPERATION MANUALSolectria
Solectria
PVI3000SResidential/Commercial Grid-Tied Photovoltaic Inverter INSTALLATION AND OPERATION MANUALSolectria
Solectria

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar